RS-1142
  • RS-1142

Surface mounted socket RS-1142

Description:

16A 3P+E 6h/380V-415V~
IP67 Surface mounted socket.
4 pin industry socket used for outdoor.

Structure size: (mm)

TYPE NAME PHOTO SPECIFICATION
RS-1142 Wall socket 16A
3P+E
380-415V
IP67
Reference dimensions
a b c d e f g h h1 h2 i/φ
82 70 13 47.5 71 155 94
Notice:
h1 is for plastic box
h2 is for sheet metal box

RS-1142 drawing

Characteristics

▲ Type: RS-1142(CEIRSIEC)
Environmental information: RoHS
Executive Standard of the Product: CE NO.LVD17-7034 GB/T11918
Certificate: CE  CQC

Technical parameters:

Electrical characteristics

In rated current: 16A
▲ The rated operational voltage: AC220-415V~
▲ Withstand voltage: AC2500V~
▲ Insulation voltage: 500V d.c 1min > 5M
▲ Instantaneous impulse current: 10KA
▲ IP degree of protection: IP67
▲ Mechanical Endurance: inserted in and pulled out 50000 cycles
▲ IK:IK07
▲ Salt tolerance: 48h unrusted
▲ Acid resistance: 48h noncorrosive

Material

▲Contact Material for copper parts
Material: Brass(ROHS)
Surface treatment: electroplated nickel

▲Body
Material: Flame retardant nylon(PA) Glow-wire 650℃
Color: red + gray
Production process: injection molding

▲Contact Material for plastic parts
Material: Flame retardant nylon(PA) Glow-wire 850℃
Color: Black
Production process: injection molding

Using an environment

▲ Temperature: -25℃~70℃
▲ Humidity: 40℃, 93%

Product presentation:

Information:

Produced according to national standards: GB/T11918.1-2014, GB/T11918.2-2014,IEC60309.
Three Phase four pins,
In rated current: 16A
Ue rated operational voltage: AC380-415V~
Network frequency: 50-60Hz,
Earth position: 6h
IP degree of protection: IP67

Package

▲ Inner Box: 10pcs/box,
▲ Carton: 60pcs /carton

Product mix:

▲ RS-0142

Wiring instructions

▲ Follow the panel instructions L/+ , Grounding

Product instructions

▲ Connection: lift the socket cover and insert the plug (the gap between the plug and the socket is less than 0.3mm) so that the socket cover is clamped on the lug of the plug sheath.

▲ Exit: turn up the cover of the socket, pull out the plug horizontally with the socket, and check that the cover of the socket returns to its original position.