RS-5332
  • RS-5332

Appliance Inlet Panle Mount RS-5332

Description:

63A 2P+E 6h/380V-415V~
IP67 Concealed fixed industry plug.
3 pin single phase appliance inlet panel mount plug.

Structure size: (mm)

TYPE NAME PHOTO SPECIFICATION
RS-5332 Appliance Inlet panel mount 63A
2P+E
220-250V
IP67
Reference dimensions
a b c d e f g h h1 h2 i/φ
112 113 100 101 101 79.5 79.5 80 90 7
Notice:
h1 is for plastic box
h2 is for sheet metal box

Characteristics

▲ Type: RS-5332(CEIRSIEC)
Environmental information: RoHS
Executive Standard of the Product: CE NO.LVD17-7034 GB/T11918
Certificate: CE  CQC

Technical parameters:

Electrical characteristics

In rated current: 63A
▲ The rated operational voltage: AC200-250V~
▲ Withstand voltage: AC2500V~
▲ Insulation voltage: 500V d.c 1min > 5M
▲ Instantaneous impulse current: 10KA
▲ IP degree of protection: IP67
▲ Mechanical Endurance: inserted in and pulled out 50000 cycles
▲ IK: IK07
▲ Salt tolerance: 48h unrusted
▲ Acid resistance: 48h noncorrosive

Material

▲Contact: Contact are brass (RoHS)

▲Body
Material: Flame retardant nylon(PA) Glow-wire 650℃
Color: bule gray
Production process: injection molding

▲Contact Material for plastic parts
Material: Flame retardant nylon(PA) Glow-wire 850℃
Color: Black
Production process: injection molding

Using an environment

▲ Temperature: -25℃~70℃
▲ Humidity: 40℃, 93%

Product presentation:

Information:

Produced according to national standards: GB/T11918.1-2014, GB/T11918.2-2014, IEC60309.
Single Phase three pins, In rated current: 63A
Ue rated operational voltage: AC200-250V~
Network frequency: 50-60Hz
Earth position: 6h
IP degree of protection: 67

Package

▲ Inner Box: 2pcs/box,
▲ Carton: 20pcs/carton

Product mix:

▲ RS-2332

Wiring instructions

▲ Follow the panel instructions L/+ , Grounding

Product instructions

▲ Connection: lift the socket cover and insert the plug (the gap between the plug and the socket is less than 0.3mm) so that the socket cover is clamped on the lug of the plug sheath.

▲ Exit: turn up the cover of the socket, pull out the plug horizontally with the socket, and check that the cover of the socket returns to its original position.